Ecoer FAQs
Final Engineer Notes : We tested Honeywell T6 Pro for an Ecoer system, it did work. Honeywell tsat G->G2 (indoor unit) Honeywell tsat Y2-&g...
Mon, 14 Sep, 2020 at 9:01 AM
When in Heating, O Signal will and should be OFF When in Cooling, O signal should be ON, since the O signal sends signal to energizes the 4 way valve
Tue, 27 Oct, 2020 at 12:48 PM
When looking at our unit run in the heating cycle you want to keep an eye out for Pressure, Discharge Super Heat, and also what the Compressor and EEV are d...
Fri, 30 Oct, 2020 at 5:05 PM
Thermostat is what activates emergency heat. Outdoor unit sensors control duel fuel.
Wed, 11 Nov, 2020 at 4:09 PM
Our Air handlers and CASED COILS Can only be used in the Horizontal-Right and Vertical-Up Position. 'For those asking were that official docume...
Thu, 17 Dec, 2020 at 8:43 AM
We want to make sure to advice Homeowners to get in contact with their contractors, who will then contact us directly. Contractors are the ones who will s...
Wed, 31 Mar, 2021 at 12:35 PM
When Using the Ecoer System with the EHK Electric Heat Strips, You now connect the W signal between the Outdoor unit and the W1 at the indoor unit. Everytim...
Tue, 25 May, 2021 at 2:10 PM
When Thermostat has determined that the temperatures are satisfied it will look to break the 24 volt signal with the G signal and cut the Fan motor off. F...
Tue, 25 May, 2021 at 3:22 PM
The Ecoer Wifi Installation Manual (Attached Below) is very simple and self explanatory. HOWEVER, There is one step that will step the process for ...
Wed, 13 Oct, 2021 at 7:15 PM
The ECOER unit do not come with a filter dyer out of factory. The installer will need to add any standard heat pump filter dryer to the unit at the tim...
Thu, 13 Jan, 2022 at 3:19 PM